Installation Instructions for 45HM IDH Max® 1300 Mortise Locks
BEST ACCESS SYSTEMS
a Division of Stanley Security Solutions, Inc.
Installing the trim
12
For example, to address an IDH Max Lock with address
number 5, the binary equivalent number would be
00101 – OFF OFF ON OFF ON. See table below.
(16) (8) (4) (2) (1)
Reader
address
Switch
5
Switch
4
Switch
3
Switch
2
Switch
1
0
All off
1
ON
2
ON
3
ON ON
4
ON
5
ON ON
6
ON ON
7
ON ON ON
8
ON
9
ON ON
10
ON ON
11
ON ON ON
12
ON ON
13
ON ON ON
14
ON ON ON
15
ON ON ON ON
16
ON
17
ON ON
18
ON ON
19
ON ON ON
20
ON ON
21
ON ON ON
22
ON ON ON
23
ON ON ON ON
24
ON ON
25
ON ON ON
26
ON ON ON
27
ON ON ON ON
28
ON ON ON
29
ON ON ON ON
30
ON ON ON ON
31
ON ON ON ON ON
12345678
ON
Figure 16 DIP switches on the Control Electronics circuit
board set to reader address 5 and 38,400 bps
baud rate and not end of line.
Switches
1–5 are reader
addressing
switches
Switches
6–7 are baud rate switches
Switch 8 is the
end-of-line switch; set it to
ON if the lock is the last one
in the daisy change.